Transformer Turns Ratio Calculator
Calculators · Added
A transformer's whole behaviour follows from one number: how many turns one winding has against the other. Voltage scales with it, current scales inversely with it, and impedance scales with its square. Enter either two voltages or two winding counts, add the load, and this gives all three along with what the primary actually draws once the losses are allowed for.
How to use the transformer turns ratio calculator
- 1Choose whether you know the two voltages or the two turns counts.
- 2Enter the primary voltage, then either the secondary voltage or the winding counts.
- 3State the load as a VA rating, a secondary current or a load impedance — whichever the datasheet or the job gives you.
- 4Set the efficiency: 80 to 90% is usual for a small mains transformer, and above 97% for a large one.
Examples
A 230 V to 12 V supply
- Input
- 230 V primary, 12 V secondary, 60 VA, 90% efficient
- Result
- Ratio 19.17:1, secondary 5 A, primary 0.29 A
The primary current includes the 10% loss, so it is higher than the ideal 0.26 A.
Matching a speaker to a valve amplifier
- Input
- Turns 25:1 with an 8 Ω speaker
- Result
- Impedance ratio 625:1 — the primary sees 5 kΩ
Impedance goes as the square of the ratio, which is why output transformers are specified by impedance rather than volts.
Reading a winding count
- Input
- 1150 primary turns, 60 secondary turns, 230 V in
- Result
- 12 V out, 0.2 volts per turn
Volts per turn is the same on both windings, so it tells you what one extra turn is worth if you are rewinding.
About the transformer turns ratio calculator
Voltage up means current down, and that is not a design choice
Both windings sit on the same magnetic circuit and link the same flux, and the voltage induced in a winding is proportional to how many turns do that linking. So the voltage ratio is the turns ratio. The current relation is not an independent fact but a consequence of energy conservation: an ideal transformer neither stores nor dissipates power, so what goes in must come out, and if the voltage was multiplied by n the current must be divided by n.
This is why a transformer cannot be a source of power, however the ratio is arranged. A step-up transformer that doubles voltage halves the current available at the same instant, and the product — the volt-amps — is unchanged. It is also why a step-down transformer's secondary is wound in thick wire and its primary in thin: the low-voltage side is the high-current side.
The squared relation, which is the useful one
Impedance transforms as the square of the turns ratio, because the primary sees n times the voltage across 1/n times the current. That squaring is what makes transformers matching devices as much as voltage-changing ones. A valve output stage that wants to see 5 kΩ and an 8 Ω loudspeaker are 625 to 1 apart in impedance, which is a turns ratio of 25 to 1 — and choosing that transformer is choosing the impedance, not the voltage.
The same relation is why the grid transmits at hundreds of kilovolts. Line loss is I squared R, so cutting the current by a factor of a hundred through a 100:1 step-up cuts the loss by ten thousand. The power arriving is the same; the heat left in the cable on the way is four orders of magnitude smaller.
What the ideal model leaves out, and the safety part
Real windings have resistance, which turns some of the power into heat and makes the output voltage sag under load. Real cores have hysteresis and eddy-current losses that appear as heat whether or not anything is connected, and leakage inductance because not every field line links both windings. The efficiency figure here rolls all of those into one number to get the primary current right; it does not tell you where the heat is going or how hot the transformer will get, which is what the manufacturer's temperature rise specification is for.
A VA rating is a thermal limit rather than an electrical one. Exceed it and nothing fails immediately — the transformer simply runs hotter than the insulation is rated for, and its life falls sharply. Intermittent loads can exceed it briefly for the same reason, though how briefly depends on the mass of the core.
Mains-voltage work is genuinely dangerous. These are figures for design and diagnosis, not instructions: wiring on the primary side of anything connected to a mains supply is work for someone qualified to do it, under the wiring rules that apply where you are.
Frequently asked questions
Why does the secondary voltage measure higher than the rating with nothing connected?
Is a VA rating the same as watts?
Can I run a 60 Hz transformer on a 50 Hz supply?
What does an isolation transformer do if the ratio is 1:1?
How do I work out the turns for a winding I want to add?
Related tools
Three-Phase Power Calculator
Calculators
Convert between kW, kVA, kVAr and line current for single- and three-phase supplies, with power factor.
Voltage Converter
Converters
Convert volts, millivolts, microvolts, kilovolts, megavolts and CGS units.
Electricity Bill Calculator
Calculators
Estimate a monthly bill from appliance usage, on flat or slab tariffs.
AC BTU Calculator
Calculators
Size an air conditioner for a room, with the adjustments for sun, ceiling height, occupants and kitchens.